KFD2-SH-EX1 安全柵現(xiàn)貨直發(fā)

型號(hào): KFD2-SH-EX1

--- 產(chǎn)品參數(shù) ---

  • KFD2-SH-EX 1

--- 產(chǎn)品詳情 ---

參數(shù)表節(jié)選:的技術(shù)參數(shù)  KFD2-SH-Ex1

General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL d
Supply
ConnectionPower Rail or terminals 22+, 23+, 24-
Rated voltage20 ... 35 V DC
Ripple≤ 10 %
Rated current≤ 130 mA
Power dissipation2.1 W
Power consumptionmax. 2.3 W
Input
Connection sidefield side
Connectionterminals 10+, 12-
Open circuit voltage/short-circuit currentapprox. 8.4 V DC / approx. 11.7 mA
Lead resistance≤ 50 Ω, in hazardous area cable capacitances and inductivities are to be taken into account
Switching point 
 Relay de-energizedI < 2.1 mA and I > 5.9 mA
 Relay energized2.8 mA < I < 5.3 mA
Response delay≤ 1 ms
Output
Connection sidecontrol side
Connectionoutput I: terminals 13, 14 ; output II: terminals 15, 21 ; output III: terminals 16+, 17-
Output Irelay , signal
 Contact loading50 V AC/1 A/cos φ > 0.7; 24 V DC/1 A resistive load
 Mechanical life50 x 106 switching cycles
Output IIrelay , signal
 Contact loading50 V AC/1 A/cos φ > 0.7; 24 V DC/1 A resistive load
 Mechanical life50 x 106 switching cycles
Output IIIelectronic output, passive , fault signal
 Rated voltage10 ... 30 V DC
 Signal level1-signal: (L+) -2.5 V (7 mA, short-circuit proof) / 0-signal: blocked output
(Leakage current ≤ 10 μA)
Transfer characteristics
Switching frequency5 Hz
Galvanic isolation
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, IIIbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Indicators/settings
Display elementsLEDs
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility 
 Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Machinery Directive 
 Directive 2006/42/ECEN/ISO 13849-1:2015
Conformity
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529:2001
SafetyIEC/EN 61508:2010
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)